Abstract

In grid-connected power generation system, fast and accurate phase synchronization detection is the prerequisite of effective control. The influence of unbalanced voltage on the three-phase inverter with conventional PLL is analyzed. When the grid voltage is unbalanced, the detection of the voltage and the calculation of the phase-locked angle will produce errors, which will affect the control accuracy of the inverter. Therefore, a control strategy without PLL is proposed and a mathematical model is established to verify its feasibility. The control strategy separates the positive sequence components of the grid voltage in the dq coordinate system. By comparing the control without PLL with the conventional PLL, the simulation shows that the control strategy without PLL can quickly and accurately separate the positive sequence components from the unbalanced power grid voltage and has a better dynamic response time.

Original languageEnglish
Title of host publication2020 IEEE 9th International Power Electronics and Motion Control Conference, IPEMC 2020 ECCE Asia
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages2740-2743
Number of pages4
ISBN (Electronic)9781728153018
DOIs
StatePublished - 29 Nov 2020
Externally publishedYes
Event9th IEEE International Power Electronics and Motion Control Conference, IPEMC 2020 ECCE Asia - Nanjing, China
Duration: 29 Nov 20202 Dec 2020

Publication series

Name2020 IEEE 9th International Power Electronics and Motion Control Conference, IPEMC 2020 ECCE Asia

Conference

Conference9th IEEE International Power Electronics and Motion Control Conference, IPEMC 2020 ECCE Asia
Country/TerritoryChina
CityNanjing
Period29/11/202/12/20

Keywords

  • Grid tied inverter
  • Negative sequence current
  • Unbalanced grid
  • Without PLL