Abstract
As a natural fluid with superior environment advantages, CO2 is used to constitute a dual transcritical system to reduce performance deterioration under high gas‐cooler outlet temperature. Aiming at the system configuration, improvement potential, and optimization, the proposed system is deeply analyzed, and corresponding coupling models are presented in detail. First, the veracity of simulation models is completely verified by comparing with previous measurements. Then, the existence of the optimal intermediate temperature is validated, while the optimal values are found to increase with the augmentation in ambient and water‐feed temperatures. Moreover, the negative effects of the pinch point on the heat transfer inside the gas cooler could be greatly reduced by using the dual gas cooler. Finally, a predictive correlation for optimal intermediate temperature determination with ambient and water‐feed temperature as independent variables is proposed, which provides a theoretical basis for the proposed system to realize efficient control in the industrialization process.
| Original language | English |
|---|---|
| Article number | 309 |
| Journal | Energies |
| Volume | 13 |
| Issue number | 2 |
| DOIs | |
| State | Published - 2020 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Dual transcritical CO2 system
- Heat pump
- Optimal intermediate temperature
- Predictive correlation
- Subcooling
Fingerprint
Dive into the research topics of 'Investigation of the impact factors on the optimal intermediate temperature in a dual transcritical CO2 system with a dedicated transcritical CO2 subcooler'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver