Investigation of influencing factors of limit air-to-water ratio of cooling tower

  • Ming Xiao Jia
  • , Jun Jie Yan
  • , Tao Ning
  • , Ming Liu
  • , Gen Li
  • , Shan Zheng

Research output: Contribution to journalArticlepeer-review

1 Scopus citations

Abstract

Experimental investigation was conducted on the cooling tower test device using the outlet water temperature as evaluation index. The experimental results indicated that: the outlet water temperature decreased with the increase of air-to-water ratio, but the trend was decreasing gradually. The limit air-to-water ratio existed during the decrease of outlet water temperature. The outlet water temperature had little change when the air-to-water ratio was up to this value. The limit air-to-water ratio decreased with the increase of inlet air dry bulb temperature and wet bulb temperature, and increased with the increase of inlet water temperature. And the limit air-to-water ratio decreased with the increase of the flow rate of circulating water. Such conclusions may be advantageously used in guiding the design and operation of cooling tower.

Original languageEnglish
Pages (from-to)134-137
Number of pages4
JournalKung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics
Volume32
Issue numberSUPPL. 1
StatePublished - Jun 2011

Keywords

  • Air-to-water ratio
  • Cooling tower
  • Outlet water temperature