Interrelations between SVC voltage control and damping control

  • Jun Liu
  • , Xing Yuan Li
  • , Guang Fu Tang

Research output: Contribution to journalArticlepeer-review

27 Scopus citations

Abstract

Dynamic interaction between voltage and damping control loops of static var compensator (SVC) controller was studied by computing the electromagnetic torque in a single machine infinite-bus (SIMB) power system. It is revealed that voltage and damping control gains of SVC are interrelated in restriction of each other in order to get positive synchronous torque and damping torque simultaneously. The influence of SVC controller parameters on the system damping of the 36-bus system presented in PSASP program was also analyzed by the eigen-value theory. The conclusion is that the voltage control gain and time constant can impact the system damping, but damping control gain can only vary the damping characteristic of the power system for improving some low damp oscillation modes. The time domain simulation results validated the conclusion.

Original languageEnglish
Pages (from-to)12-17
Number of pages6
JournalZhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
Volume28
Issue number1
StatePublished - 5 Jan 2008

Keywords

  • Damp
  • Electromagnetic torque
  • Oscillation mode
  • Static var compensator

Fingerprint

Dive into the research topics of 'Interrelations between SVC voltage control and damping control'. Together they form a unique fingerprint.

Cite this