Abstract
An integrated algorithmic and heuristic technique for transition-optimised voltage and reactive power control is presented. The method seeks to provide a 'transition-optimised' voltage and reactive-power control method. Essentially it considers voltage and reactive power control as a time-based scheduling problem, with the intention of avoiding unnecessary changes in status and output of reactive control plant. The demand profile is classified adaptively using a heuristic iteration method through evaluating the standard deviation and the range of the sequence of load-demand points. Furthermore, an algorithmic transition-optimised model of the volt/VAr control is then presented based on demand-pattern classification. The solution algorithm and different control strategies are studied in the transition optimisation. Case studies illustrate that the integrated algorithmic and heuristic technique for transition-optimised voltage and reactive power control not only effectively reduces power losses, but also greatly simplifies control operations.
| Original language | English |
|---|---|
| Pages (from-to) | 205-210 |
| Number of pages | 6 |
| Journal | IEE Proceedings: Generation, Transmission and Distribution |
| Volume | 153 |
| Issue number | 2 |
| DOIs | |
| State | Published - Mar 2006 |
Fingerprint
Dive into the research topics of 'Integration of algorithmic and heuristic techniques for transition-optimised voltage and reactive power control'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver