Insulation condition evaluation of 750 kV power transformers based on frequency domain spectroscopy

  • Shuang Suo Yang
  • , Guan Jun Zhang
  • , Ming Dong
  • , Jian Lin Wei
  • , Shi Qiang Wang
  • , Zheng Yu
  • , Yu Chang Feng

Research output: Contribution to journalArticlepeer-review

14 Scopus citations

Abstract

The reliability of oil-immersed power transformers depends on the insulation system to a large extent, and the lifetime decrease with the deterioration of the insulation system. Therefore, insulation diagnosis and lifetime evaluation for oil-immersed transformers are necessary. In this paper, diagnostics of transform insulation are analyzed, and a new diagnostic technique based on frequency domain spectroscopy (FDS) is presented. The 750 kV transform operated in Lanzhou East Substation is measured on-site with the FDS method. The experimental results show that the moisture content in transformer pressboard is eligible, and its insulation condition is well. And the experimental results are consistent with those of the conventional preventive test. The validity of FDS method is proved, and it is promising as a novel preventive test method.

Original languageEnglish
Pages (from-to)16-20
Number of pages5
JournalGaoya Dianqi/High Voltage Apparatus
Volume46
Issue number4
StatePublished - 2010

Keywords

  • Aging
  • Dielectric response
  • Frequency domain spectroscopy
  • Insulation
  • Oil-immersed transformer

Fingerprint

Dive into the research topics of 'Insulation condition evaluation of 750 kV power transformers based on frequency domain spectroscopy'. Together they form a unique fingerprint.

Cite this