TY - JOUR
T1 - Influence of sensible cooling load on indoor air distribution in an office room with ceiling cooling and mixing ventilation
AU - Wu, Xiaozhou
AU - Wang, Haichao
AU - Gao, Jie
AU - Wang, Fenghao
N1 - Publisher Copyright:
© The Author(s) 2020.
PY - 2021/8
Y1 - 2021/8
N2 - A mixing ventilation system integrated with a ceiling cooling system is a potential advanced heating, ventilation and air conditioning system for modern office buildings with a high sensible cooling load. This paper presents an evaluation of the effect of sensible cooling load on the indoor air distribution in a typical office room with mixing ventilation and ceiling cooling. The vertical distributions of indoor air temperature, air velocity and contaminant (CO2) concentration were evaluated by the vertical air temperature difference, turbulence intensity and contaminant removal effectiveness. The results showed that when the chilled ceiling surface temperature was increased from 15.0°C to 23.0°C and supply air temperature was decreased from 22.0°C to 19.0°C, the average vertical air temperature difference, turbulence intensity and contaminant removal effectiveness were 0.2°C–0.3°C, 27%–32% and 0.53–0.81 as both internal and external sensible cooling loads were 41.5 W/m2. Moreover, these evaluation indices varied slightly as the external sensible cooling load was increased from 41.5 W/m2 to 69.5 W/m2, whereas they varied greatly as the internal sensible cooling load was increased from 41.5 W/m2 to 69.5 W/m2. Hence, the external sensible cooling load could slightly affect the indoor air distribution, whereas the internal sensible cooling load could clearly affect the indoor air distribution in an office room with mixing ventilation and ceiling cooling.
AB - A mixing ventilation system integrated with a ceiling cooling system is a potential advanced heating, ventilation and air conditioning system for modern office buildings with a high sensible cooling load. This paper presents an evaluation of the effect of sensible cooling load on the indoor air distribution in a typical office room with mixing ventilation and ceiling cooling. The vertical distributions of indoor air temperature, air velocity and contaminant (CO2) concentration were evaluated by the vertical air temperature difference, turbulence intensity and contaminant removal effectiveness. The results showed that when the chilled ceiling surface temperature was increased from 15.0°C to 23.0°C and supply air temperature was decreased from 22.0°C to 19.0°C, the average vertical air temperature difference, turbulence intensity and contaminant removal effectiveness were 0.2°C–0.3°C, 27%–32% and 0.53–0.81 as both internal and external sensible cooling loads were 41.5 W/m2. Moreover, these evaluation indices varied slightly as the external sensible cooling load was increased from 41.5 W/m2 to 69.5 W/m2, whereas they varied greatly as the internal sensible cooling load was increased from 41.5 W/m2 to 69.5 W/m2. Hence, the external sensible cooling load could slightly affect the indoor air distribution, whereas the internal sensible cooling load could clearly affect the indoor air distribution in an office room with mixing ventilation and ceiling cooling.
KW - Ceiling cooling
KW - Indoor air distribution
KW - Mixing ventilation
KW - Sensible cooling load
UR - https://www.scopus.com/pages/publications/85086090607
U2 - 10.1177/1420326X20924819
DO - 10.1177/1420326X20924819
M3 - 文章
AN - SCOPUS:85086090607
SN - 1420-326X
VL - 30
SP - 957
EP - 969
JO - Indoor and Built Environment
JF - Indoor and Built Environment
IS - 7
ER -