TY - GEN
T1 - Improved Temperature Calculation Model for High Voltage Direct Current Submarine Cables Considering Insulation Leakage Current and Thermomechanical Stress
AU - Zhang, Wenjiao
AU - Hu, Yuxiao
AU - Shi, Chaoqun
AU - Zhang, Xiaojing
AU - Xu, Yang
N1 - Publisher Copyright:
© 2026 IEEE.
PY - 2026
Y1 - 2026
N2 - With the rapid development of offshore wind power, high voltage direct current (HVDC) submarine cables enable long-distance, low-loss, and efficient power transmission. During long-term operation, submarine cables are affected by electrical, thermal, mechanical, and environmental conditions. Compared with land cables, submarine cables have a more complex structure and face more changeable conditions. Thus, accurate calculation of the temperature distribution of submarine cables is essential for precise state monitoring. In this study, the thermal conductivity and related parameters were defined as temperature-dependent functions in the material settings. The influence of insulation leakage current on temperature calculations was considered. Then, based on a conventional electro-thermal model, a coupling relationship between the stress and thermal fields was established in COMSOL. Finally, temperature rise experiments were conducted using a 525 kV submarine cable under different load conditions to verify the accuracy of the proposed model. Temperatures at the conductor, insulation, insulation shield, lead sheath, and outer sheath were measured. Compared with the electrothermal model, the simulation accuracy of the proposed model was improved from 90.0% to 96.0%.
AB - With the rapid development of offshore wind power, high voltage direct current (HVDC) submarine cables enable long-distance, low-loss, and efficient power transmission. During long-term operation, submarine cables are affected by electrical, thermal, mechanical, and environmental conditions. Compared with land cables, submarine cables have a more complex structure and face more changeable conditions. Thus, accurate calculation of the temperature distribution of submarine cables is essential for precise state monitoring. In this study, the thermal conductivity and related parameters were defined as temperature-dependent functions in the material settings. The influence of insulation leakage current on temperature calculations was considered. Then, based on a conventional electro-thermal model, a coupling relationship between the stress and thermal fields was established in COMSOL. Finally, temperature rise experiments were conducted using a 525 kV submarine cable under different load conditions to verify the accuracy of the proposed model. Temperatures at the conductor, insulation, insulation shield, lead sheath, and outer sheath were measured. Compared with the electrothermal model, the simulation accuracy of the proposed model was improved from 90.0% to 96.0%.
UR - https://www.scopus.com/pages/publications/105050707510
U2 - 10.1109/ICD64907.2026.11664882
DO - 10.1109/ICD64907.2026.11664882
M3 - 会议稿件
AN - SCOPUS:105050707510
T3 - 6th IEEE International Conference on Dielectrics: Next Generation Sustainable Dielectrics, ICD 2026
SP - 73
EP - 76
BT - 6th IEEE International Conference on Dielectrics
A2 - Chaudhary, Sunny
A2 - Saeedi, Istebreq
A2 - Tillotson, Liz
A2 - Vryonis, Orestis
A2 - Callender, George
A2 - Zaghari, Bahareh
A2 - Deeth-Kelt, Lauren
PB - Institute of Electrical and Electronics Engineers Inc.
T2 - 6th IEEE International Conference on Dielectrics, ICD 2026
Y2 - 21 June 2026 through 25 June 2026
ER -