Skip to main navigation Skip to search Skip to main content

Impact of overhead air supply layout on the thermal performance of a container data center

  • National Yang Ming Chiao Tung University

Research output: Contribution to journal › Article › peer-review

8 Scopus citations

Abstract

This study focused on the improved designs of airflow management in container data centers having overhead air supply. The computational fluid dynamics (CFD) model is first validated with experimental results. Then, the impact of grille diameter, deflector angle, and air supply layout on the data center thermal performance is investigated. The results show that the larger grille diameter may reduce the volumetric flowrate through the upstream grille, causing insufficient air supply and strong hot-air recirculation at the first rack A1. By decreasing the grille diameter from 335mm to 235 mm, the average rack cooling index (RCI) and supply heat index (SHI) can be improved from 25.4% and 0.292 to 65% and 0.258, respectively. However, implementing small diameter grilles is not an economic way for data center performance improvement as far as the energy consumption is concerned due to the high pumping power. Meanwhile, raising the deflector angle below 30 deg in grille S1 can provide moderate improvement on temperature of the A1 rack. A further rise in the deflector to 40 deg may impose severe deterioration with a pronounced hot-spot area. The data center performance can be improved by changing from center-cold-aisle arrangement to center-hot-aisle layout. The layout provides much higher return air temperature and the RCI and SHI can be improved by 32.7% and 34.5%, respectively.

Original languageEnglish
Article number011008
JournalJournal of Electronic Packaging
Volume142
Issue number1
DOIs
StatePublished - Mar 2020
Externally publishedYes

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • Air supply layout
  • CFD
  • Pumping power
  • RCI and SHI
  • Simulated container data center

Fingerprint

Dive into the research topics of 'Impact of overhead air supply layout on the thermal performance of a container data center'. Together they form a unique fingerprint.

Cite this