Hierarchical load-following control of modular fluoride-salt-cooled high-temperature reactor with supercritical carbon dioxide Brayton cycle

  • Shichang Yun
  • , Dalin Zhang
  • , Wenxiang Gao
  • , Xinyu Li
  • , Xingguang Zhou
  • , Wenxi Tian
  • School of Nuclear Science and Technology
  • Xi'an Jiaotong University

Research output: Contribution to journal › Article › peer-review

Abstract

Efficient load following in reactor-coupled supercritical carbon dioxide (sCO₂) cycles requires both feasible operating points and dynamically achievable transitions. This study develops a hierarchical control framework for a recompression sCO₂ cycle coupled to a 125-MWt small modular fluoride-salt-cooled high-temperature reactor. Open-loop diagnosis, quasi-steady screening, and transient simulation are combined to select efficient target operating points and design their transition paths without prescribing a preferred actuator combination. Screening considers constraints on power, pressure, temperature, compressor stability, and actuators, together with a preliminary quasi-steady stress limit for the intermediate heat exchanger. The resulting fixed-speed operating map covers 20%–100% load. Inventory-only control provides feasible final operating points from approximately 42% to 100% load, whereas inventory–throttling control is the most efficient strictly feasible combination examined over 20%–40% load. A 45% supervisory threshold selects direct turbine-bypass-to-inventory handover at or above this load and throttle-assisted handover below it. Simulations of 100%–80% and 100%–20% load reductions at 5 percentage points per minute employ rapid turbine-bypass tracking, followed by inventory regulation and throttle-assisted handover to inventory–throttling regulation, respectively. Absolute load-tracking deviations remain within 0.22 and 0.10 percentage points throughout the two transients, and final cycle efficiencies reach 48.59% and 32.95%, respectively. During the 20% load case, cycle pressure remains within 7.50–26.82 MPa and the minimum compressor surge margin is 24.53%. By separating target operating-point selection from transient control-path design, the framework provides a model-based approach to scheduled load following and deep peak shaving.

Original languageEnglish
Article number133323
JournalApplied Thermal Engineering
DOIs
StateAccepted/In press - 2026

Keywords

  • Hierarchical control
  • Load-following control
  • Operating-domain screening
  • sCO₂ Brayton cycle
  • Small modular fluoride-salt-cooled reactor
  • Transient analysis