Skip to main navigation Skip to search Skip to main content

Experimental research on the current limiting performance of liquid metal current limiter

  • Xi'an Jiaotong University

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

1 Scopus citations

Abstract

This paper focuses on the experimental research of current limiting performance of a liquid metal current limiter based on pinch effects. A specially designed test setup is adopted to observe the dynamic process of the fluid pinch process. From the frames obtained by high-speed camera, its pinch mechanism is revealed. Furthermore, the arc behavior is studied, which can be classified into four stages: arc ignition, arc elongation, arc constriction and arc extinction. Finally, the impacts on the arc properties from the inner pressure owing to arc burning in the enclosure is discussed and analyzed. It indicates that if this pressure is great enough, the liquid metal probably driven to flow back into the channel to reconnect the circuit before current zero.

Original languageEnglish
Title of host publication2015 3rd International Conference on Electric Power Equipment - Switching Technology, ICEPE-ST 2015
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages207-211
Number of pages5
ISBN (Electronic)9781467374149
DOIs
StatePublished - 29 Dec 2015
Event3rd International Conference on Electric Power Equipment - Switching Technology, ICEPE-ST 2015 - Busan, Korea, Republic of
Duration: 25 Oct 201528 Oct 2015

Publication series

Name2015 3rd International Conference on Electric Power Equipment - Switching Technology, ICEPE-ST 2015

Conference

Conference3rd International Conference on Electric Power Equipment - Switching Technology, ICEPE-ST 2015
Country/TerritoryKorea, Republic of
CityBusan
Period25/10/1528/10/15

Keywords

  • arc behavior
  • current limiting
  • liquid metal
  • pinch effect
  • pressure measurement

Fingerprint

Dive into the research topics of 'Experimental research on the current limiting performance of liquid metal current limiter'. Together they form a unique fingerprint.

Cite this