Abstract

Many research studies have been conducted on the performance of shell and tube heat exchanger with helical baffles because of its lower shell-side pressure drop, lower fouling resistance and lower operation and maintenance cost. But the extension of those studies into practical application is limited because of the additional effects caused by the small-size model. In this paper, the performance of shell-and-tube oil coolers with overlapped helical baffles and segmental baffles is compared experimentally, and both of the oil coolers are practical products. The results show that the OCHB (Oil Cooler with Helical Baffles) gets lower shell side pressure drop and higher heat transfer coefficient per unit pressure drop at fixed volume flow rate than the OCSB (Oil Cooler with Segmental Baffles). Based on the experimental data, it can be predicted that with proper design the OCHB can get better heat transfer performance than OCSB. The present studies are beneficial for the design and practical operation of OCSB and OCHB.

Original languageEnglish
Pages (from-to)336-343
Number of pages8
JournalApplied Thermal Engineering
Volume58
Issue number1-2
DOIs
StatePublished - 2013

Keywords

  • Keywords Oil cooler Helical baffle Segmental baffle Pressure drop Heat transfer

Fingerprint

Dive into the research topics of 'Experimental performance comparison of shell-and-tube oil coolers with overlapped helical baffles and segmental baffles'. Together they form a unique fingerprint.

Cite this