TY - JOUR
T1 - Experimental investigations on the working performance of a sliding vane pump in the electronic direct cooling system
AU - Yin, Xiang
AU - Cao, Feng
AU - Wang, Jing
AU - Fang, Jianmin
AU - Wang, Xiaolin
N1 - Publisher Copyright:
© 2020, © 2020 ASHRAE.
PY - 2020/4/20
Y1 - 2020/4/20
N2 - In the two-phase electronic direct cooling system, the traditional centrifugal pump often has low efficiency, and it heavily suffers from the cavitation problem. To deal with this problem, a sliding vane rotary pump was developed and tested in a two-phase electronic evaporative cooling system, and the working performance was investigated and analyzed based on the experimental data. The effect of the suction port size was studied. In a two-phase cooling system, the volumetric efficiency decreased with the rotary speed. The discharge valve had no fatal influence on the stable working performance of the pump. However, it highly affected the volumetric efficiency in high rotary speed while it acted insignificantly in the low speed. A stable cooling result could be quickly obtained during the change of the heat flux with the driving of the sliding vane pump, and a minor dependence between flow rates was detected, which was caused by the pressure rise. Therefore, the sliding vane pump was able to be an alternative pump for the two-phase electronic direct cooling system.
AB - In the two-phase electronic direct cooling system, the traditional centrifugal pump often has low efficiency, and it heavily suffers from the cavitation problem. To deal with this problem, a sliding vane rotary pump was developed and tested in a two-phase electronic evaporative cooling system, and the working performance was investigated and analyzed based on the experimental data. The effect of the suction port size was studied. In a two-phase cooling system, the volumetric efficiency decreased with the rotary speed. The discharge valve had no fatal influence on the stable working performance of the pump. However, it highly affected the volumetric efficiency in high rotary speed while it acted insignificantly in the low speed. A stable cooling result could be quickly obtained during the change of the heat flux with the driving of the sliding vane pump, and a minor dependence between flow rates was detected, which was caused by the pressure rise. Therefore, the sliding vane pump was able to be an alternative pump for the two-phase electronic direct cooling system.
UR - https://www.scopus.com/pages/publications/85078402028
U2 - 10.1080/23744731.2020.1712947
DO - 10.1080/23744731.2020.1712947
M3 - 文章
AN - SCOPUS:85078402028
SN - 2374-4731
VL - 26
SP - 484
EP - 491
JO - Science and Technology for the Built Environment
JF - Science and Technology for the Built Environment
IS - 4
ER -