N2 - Because of great harmfulness of greenhouse effect, SF6 gas has to be limited, and it is necessary to develop high voltage vacuum circuit breakers to replace SF6 circuit breakers. Current chop is a well-known phenomenon for vacuum interrupters and results in high overvoltage. The chopping current depends not only on material parameters and gap parameters, but also on the parameters of the electrical network. In this paper, current chop phenomena of 126kV single break vacuum interrupters have been researched in an experimental circuit where current is limited either by a resistor or an inductance. In the experiment, contact gap is 20mm or 30mm and arcing current is 32A or 66A. A serial of experiment has been carried out for two 126kV vacuum interrupters with CuCr55 and CuCrTa contact material. It has been found that the current chop phenomenon shows a significant dependence on contact materials, arc current and the capacitance parallel to the switching gap. The results showed that the chopping current of CuCrTa contact material is lower than that of CuCr55 contact material for 126kV vacuum interrupters.
AB - Because of great harmfulness of greenhouse effect, SF6 gas has to be limited, and it is necessary to develop high voltage vacuum circuit breakers to replace SF6 circuit breakers. Current chop is a well-known phenomenon for vacuum interrupters and results in high overvoltage. The chopping current depends not only on material parameters and gap parameters, but also on the parameters of the electrical network. In this paper, current chop phenomena of 126kV single break vacuum interrupters have been researched in an experimental circuit where current is limited either by a resistor or an inductance. In the experiment, contact gap is 20mm or 30mm and arcing current is 32A or 66A. A serial of experiment has been carried out for two 126kV vacuum interrupters with CuCr55 and CuCrTa contact material. It has been found that the current chop phenomenon shows a significant dependence on contact materials, arc current and the capacitance parallel to the switching gap. The results showed that the chopping current of CuCrTa contact material is lower than that of CuCr55 contact material for 126kV vacuum interrupters.
UR - https://www.scopus.com/pages/publications/78650508138
U2 - 10.1109/DEIV.2010.5625815
DO - 10.1109/DEIV.2010.5625815
M3 - 会议稿件
AN - SCOPUS:78650508138
SN - 9781424483655
T3 - Proceedings - International Symposium on Discharges and Electrical Insulation in Vacuum, ISDEIV
SP - 237
EP - 240
BT - ISDEIV 2010 - 24th International Symposium on Discharges and Electrical Insulation in Vacuum, Proceedings
T2 - 24th International Symposium on Discharges and Electrical Insulation in Vacuum, ISDEIV 2010
Y2 - 30 August 2010 through 3 September 2010
ER -