Abstract
The substantial inertia of the boiler restricts the flexibility of circulating fluidized bed (CFB) power units. To enhance the load ramp-up capability of the CFB power unit, we proposed a novel control strategy considering the spatial-temporal evolution of its internal stored energy. A dynamic model of the subcritical CFB power unit with a capacity of 300 MW was developed, incorporating the mechanism and control modules. By analyzing the spatial-temporal evolution of the stored energy in bed material, flue gases, refractory materials, economizer, evaporation subsystem, superheater subsystem, reheater subsystem, and turbine subsystem, we identified that the over-utilization of chemical and thermal stored energy in the bed materials is the primary factor restricting load ramp-up, while the thermal stored energy of the economizer is suitable for further utilization. Under the optimized control strategy that utilizes deviations of stored energy per mass of bed materials as a feedforward mechanism, the deviations of the key operating parameters during the load ramp-up process are significantly reduced, and the load ramp-up rate of the subcritical CFB power unit can be improved from 2.0 % Pe/min to 3.0 % Pe/min.
| Original language | English |
|---|---|
| Article number | 132571 |
| Journal | Energy |
| Volume | 307 |
| DOIs | |
| State | Published - 30 Oct 2024 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- CFB power unit
- Control strategy
- Dynamic model
- Flexibility
- Internal stored energy
- Load ramp-up
Fingerprint
Dive into the research topics of 'Enhancing the load ramp-up capability of the subcritical CFB power unit by considering the evolution of internal stored energy'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver