Skip to main navigation Skip to search Skip to main content

Energization Transient Suppression of 750 kV AC Filters Using a Preinsertion Resistor Circuit Breaker With a Controlled Switching Device

  • Xiaohui Chen
  • , Chunying He
  • , Junbo Deng
  • , Xiaoguang Zhu
  • , Guanjun Zhang
  • , Hui Ni
  • , Feiyue Ma
  • , Lei Chen
  • Xi'an Jiaotong University
  • Ningxia Electric Power Company

Research output: Contribution to journalArticlepeer-review

13 Scopus citations

Abstract

Different from typical circuit breakers, breakers used to switch AC filters in convertor stations have to operate frequently according to the real-time operation mode and daily load changes. Therefore, the performance of filter breakers decreases very quickly, which leads to frequent accidents. Both preinsertion resistors and controlled switching devices can suppress switching transients. In this paper, a comparative analysis of whether a controlled switching device and preinsertion resistor should be adopted is carried out using PSCAD. The transient is calculated as the combined result of the switching angle and preinsertion resistor value, and the optimal configurations are proposed. After determining the resistor value and whether a controlled switching device should be included, the reference voltage of the arrester should be reevaluated.

Original languageEnglish
Pages (from-to)3381-3390
Number of pages10
JournalIEEE Transactions on Power Delivery
Volume37
Issue number4
DOIs
StatePublished - 1 Aug 2022

Keywords

  • AC filter
  • controlled switching
  • insulation coordination
  • preinsertion resistor
  • switching transients

Fingerprint

Dive into the research topics of 'Energization Transient Suppression of 750 kV AC Filters Using a Preinsertion Resistor Circuit Breaker With a Controlled Switching Device'. Together they form a unique fingerprint.