Compared with traditional mineral insulating oil, natural ester insulating liquid has become an ideal alternative medium for transformer insulation due to its high fire point and biodegradability. The retrofilling of transformers with natural esters has been gradually promoted and applied. However, there are few studies on the influence of natural ester retrofilling on the insulation strength and heat dissipation performance of distribution transformers. Moreover, the current process flow of factory-returned retrofilling tests requires a lot of time and manpower, which is difficult to meet the requirements of time-limited power outage operations for distribution transformers. This study carries out retrofilling tests on three 630 kVA/10 kV distribution transformers with natural ester using an integrated device. Electric field and thermal simulations are conducted before retrofilling to evaluate the risk of natural ester filled in serviced mineral oil distribution transformers. After retrofilling, the properties of insulating liquid were tested and compared with that before retrofilling. The routine tests and heat run tests were carried out on the transformers. The results show that the insulation resistance of the three transformers decreased after retrofilling, but still above 300 MΩ meeting the requirement limits. The fire point were all greater than 300 °C after retrofilling, meeting the K-class flame retardant requirements, and the residual mineral oil content were estimated from 3.07 wt% to 5.17 wt%. These three retrofilled transformers were all connected to the grid.

Original languageEnglish
Title of host publicationThe Proceedings of the 20th Annual Conference of China Electrotechnical Society
EditorsQingxin Yang, Dianguo Xu, Xuerong Ye, Qiuyue Nie, Yueshi Guan
PublisherSpringer Science and Business Media Deutschland GmbH
Pages311-324
Number of pages14
ISBN (Print)9789819573332
DOIs
StatePublished - 2026
Event20th Annual Conference of China Electrotechnical Society, ACCES 2025 - Harbin, China
Duration: 19 Sep 202521 Sep 2025

Publication series

NameLecture Notes in Electrical Engineering
Volume1564 LNEE
ISSN (Print)1876-1100
ISSN (Electronic)1876-1119

Conference

Conference20th Annual Conference of China Electrotechnical Society, ACCES 2025
Country/TerritoryChina
CityHarbin
Period19/09/2521/09/25

Keywords

  • Distribution transformer
  • Insulation resistance
  • Natural ester
  • Retrofilling
  • Thermal simulation

Fingerprint

Dive into the research topics of 'Electric Field and Thermal Simulation and Validated Practice of Natural Ester Retrofilled 10 kV Transformers'. Together they form a unique fingerprint.

Cite this