N2 - Currently, the common evaporator model based on the moving boundary method ignores the inlet specific enthalpy time derivative, and then yields a mass conservation error in the calculation, which may further reduce the dynamic simulation precision of the evaporator and whole system. To solve this problem, the common evaporator model is modified by introducing an additional input variable, i.e. evaporator inlet specific enthalpy time derivative. The computational results indicate that the modified evaporator model can perfectly eliminate the mass conservation error compared to the common evaporator model. The simulation results based on the common model and the modified model are compared with the experimental data, which reveals that the results from the modified model have better agreement with the experimental data. Under the considered condition, the modified model can reduce the simulation error of average heating capacity from 8.61% to 3.82% compared with the common model. The transient response of the modified model to the step change of the EEV opening degree is also verified with the test. And both the response speeds and numerical values of the evaporating pressure and refrigerant mass flow rate show good agreement. The effects of the evaporator air velocity and the compressor frequency on the system performance are theoretically investigated based on the modified model. The increase of the evaporator air velocity always contributes to the performance improvement of the whole system, but this positive effect become very small when the air velocity exceeds 3 m/s. As the compressor frequency increases from 40 Hz to 60 Hz, the average heating capacity and power consumption increase by 39.62% and 9.79%, respectively.
AB - Currently, the common evaporator model based on the moving boundary method ignores the inlet specific enthalpy time derivative, and then yields a mass conservation error in the calculation, which may further reduce the dynamic simulation precision of the evaporator and whole system. To solve this problem, the common evaporator model is modified by introducing an additional input variable, i.e. evaporator inlet specific enthalpy time derivative. The computational results indicate that the modified evaporator model can perfectly eliminate the mass conservation error compared to the common evaporator model. The simulation results based on the common model and the modified model are compared with the experimental data, which reveals that the results from the modified model have better agreement with the experimental data. Under the considered condition, the modified model can reduce the simulation error of average heating capacity from 8.61% to 3.82% compared with the common model. The transient response of the modified model to the step change of the EEV opening degree is also verified with the test. And both the response speeds and numerical values of the evaporating pressure and refrigerant mass flow rate show good agreement. The effects of the evaporator air velocity and the compressor frequency on the system performance are theoretically investigated based on the modified model. The increase of the evaporator air velocity always contributes to the performance improvement of the whole system, but this positive effect become very small when the air velocity exceeds 3 m/s. As the compressor frequency increases from 40 Hz to 60 Hz, the average heating capacity and power consumption increase by 39.62% and 9.79%, respectively.
KW - Dynamic simulation
KW - Experimental verification
KW - Heat pump
KW - Modified evaporator model
UR - https://www.scopus.com/pages/publications/85052330135
U2 - 10.1016/j.applthermaleng.2018.08.085
DO - 10.1016/j.applthermaleng.2018.08.085
M3 - 文章
AN - SCOPUS:85052330135
SN - 1359-4311
VL - 144
SP - 469
EP - 478