TY - JOUR
T1 - Development and Type Test of a Single-Break 126-kV/40-kA-2500-A Vacuum Circuit Breaker
AU - Yao, Xiaofei
AU - Wang, Jianhua
AU - Geng, Yingsan
AU - Yan, Jing
AU - Liu, Zhiyuan
AU - Yao, Jianjun
AU - Liu, Ping
N1 - Publisher Copyright:
© 1986-2012 IEEE.
PY - 2016/2
Y1 - 2016/2
N2 - The objective of this paper is to present a 126-kV/40-kA-2500-A single-break vacuum circuit breaker (VCB) and its type test results based on the IEC 62271-100: 2006 and GB1984-2003 standards. A single-break 126-kV vacuum interrupter (VI), with a pair of 2/3 coil-type contacts, is used in the 126-kV VCB. The external insulation of the VI is provided by SF6 at 0.1 MPa. A spring-type operating mechanism is used to provide a closing velocity of 1.15 m/s, which is an average velocity for 4 mm before the moving contact mates with the stationary contact. The opening velocity within 20 mm, which is 1/3 of a full contact stroke of 60 mm, is 3.5 m/s. Two kinds of test circuits are used in the type tests to verify the making and breaking capabilities of this 126-kV VCB prototype. One is a direct test circuit for test duty cycles, such as out-of-phase making and breaking test duties, that is, OP1 and OP2; capacitive current switching test of class C1, that is, CC1/LC1 and CC2/LC2. The other is a synthetic circuit, used for tests, such as the terminal fault test, the short-line fault test, the double earth fault test, and the electrical endurance test of class E2. The dielectric tests of a 230-kV/1 min power frequency voltage withstand test and a 550-kV lightning impulse voltage withstand test were used to verify the dielectric withstand performance of the VCB. Experiment results presented in this paper showed that the 126-kV/40 kA-2500 A single-break VCB passed the type tests according to IEC 62271-100 and GB1984-2003.
AB - The objective of this paper is to present a 126-kV/40-kA-2500-A single-break vacuum circuit breaker (VCB) and its type test results based on the IEC 62271-100: 2006 and GB1984-2003 standards. A single-break 126-kV vacuum interrupter (VI), with a pair of 2/3 coil-type contacts, is used in the 126-kV VCB. The external insulation of the VI is provided by SF6 at 0.1 MPa. A spring-type operating mechanism is used to provide a closing velocity of 1.15 m/s, which is an average velocity for 4 mm before the moving contact mates with the stationary contact. The opening velocity within 20 mm, which is 1/3 of a full contact stroke of 60 mm, is 3.5 m/s. Two kinds of test circuits are used in the type tests to verify the making and breaking capabilities of this 126-kV VCB prototype. One is a direct test circuit for test duty cycles, such as out-of-phase making and breaking test duties, that is, OP1 and OP2; capacitive current switching test of class C1, that is, CC1/LC1 and CC2/LC2. The other is a synthetic circuit, used for tests, such as the terminal fault test, the short-line fault test, the double earth fault test, and the electrical endurance test of class E2. The dielectric tests of a 230-kV/1 min power frequency voltage withstand test and a 550-kV lightning impulse voltage withstand test were used to verify the dielectric withstand performance of the VCB. Experiment results presented in this paper showed that the 126-kV/40 kA-2500 A single-break VCB passed the type tests according to IEC 62271-100 and GB1984-2003.
KW - Type test
KW - vacuum circuit breaker (VCB)
KW - vacuum interrupter
UR - https://www.scopus.com/pages/publications/84962438819
U2 - 10.1109/TPWRD.2015.2456033
DO - 10.1109/TPWRD.2015.2456033
M3 - 文章
AN - SCOPUS:84962438819
SN - 0885-8977
VL - 31
SP - 182
EP - 190
JO - IEEE Transactions on Power Delivery
JF - IEEE Transactions on Power Delivery
IS - 1
M1 - 7277075
ER -