Skip to main navigation Skip to search Skip to main content

Design and thermofluidic performance of multi-level embedded cooling structures for multi-chip array electronic systems

  • Xi'an Jiaotong University
  • CAS - Institute of Microelectronics

Research output: Contribution to journal › Article › peer-review

7 Scopus citations

Abstract

With the continuous increase in the heat flux of multi-chip array electronic systems, conventional microchannel heat sinks encounter difficulties in meeting the heat dissipation requirements of such systems due to high thermal resistance and non-uniform flow distribution. To address the design challenges of efficient thermal management structures for large-scale multi-chip array electronic systems, this study proposes a multi-level cooling structure design method. Taking a four-chip array as the basic unit, the cooling structure of large-scale multi-chip array electronic systems is divided into multiple four-chip array unit cooling structures and a manifold structure used for the distribution and collection of the coolant among the four-chip array unit cooling structures, thereby realizing the modular assembly of embedded cooling structures for large-scale multi-chip array electronic systems. Based on this multi-level cooling structure design method, a test device composed of four-chip array unit cooling structure samples and a manifold structure was developed, and experimental tests were conducted on the four-chip array. The experimental results indicate that, at a heat flux of 160.5 W·cm−2 and a coolant flow rate of 600 ml·min−1, the average thermal resistance of the test device is 0.037 cm2·K·W−1. At a flow rate of 400 ml·min−1, the average temperature non-uniformity is 1.62 °C, indicating favorable heat dissipation performance and temperature uniformity. Based on the cooling structure design of the experimental device, an embedded cooling structure was developed for a 36-chip array electronic system. The cooling structure was optimized through flow resistance analysis and model simplification by means of simulation. The simulation results show that the optimized embedded cooling structure for the 36-chip array electronic system exhibits excellent thermal dissipation performance, flow performance, and temperature uniformity. At an inlet flow rate of 7 L·min−1 and a total thermal power of 15 kW, the maximum temperature of the heat sources in each chip remains below 80°C, with the maximum temperature difference of merely 1.51°C, the maximum temperature non-uniformity of 0.53 °C, and the pressure drop of only 15.28 kPa. This study provides a method for the design of embedded cooling structures in large-scale multi-chip array electronic systems.

Original languageEnglish
Article number127803
JournalApplied Thermal Engineering
Volume279
DOIs
StatePublished - 15 Nov 2025

Keywords

  • Efficient heat dissipation
  • Embedded cooling
  • Flow distribution
  • Large-scale multi-chip array electronic systems
  • Multi-level design
  • Optimization design

Fingerprint

Dive into the research topics of 'Design and thermofluidic performance of multi-level embedded cooling structures for multi-chip array electronic systems'. Together they form a unique fingerprint.

Cite this