Coupling model of AC filter branch in SF6circuit breaker during the break process

  • Zaixing Peng
  • , Kai Liu
  • , Yanwei Nan
  • , Song Wang
  • , Fei Yang
  • , Hao Sun
  • , Yuan La

Research output: Contribution to journalArticlepeer-review

4 Scopus citations

Abstract

In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the current at power frequency (50 Hz), power frequency combining the 11th harmonic and power frequency combining the 24th harmonic show that the high-order harmonic current would lead to higher decreasing rate of current before current-zero period. In addition, the influence of arc on the amplitude of high-order harmonic current is not negligible. Thus, the coupling of arc with AC filter branch circuit is quite necessary in the numerical modeling of the circuit breaker in the AC filter branch at the high voltage direct current converter station.

Original languageEnglish
Article number125402
JournalPlasma Science and Technology
Volume22
Issue number12
DOIs
StatePublished - Dec 2020
Externally publishedYes

Keywords

  • AC filter branch
  • SFcircuit breaker
  • arc characteristics

Fingerprint

Dive into the research topics of 'Coupling model of AC filter branch in SF6circuit breaker during the break process'. Together they form a unique fingerprint.

Cite this