Abstract

In order to assess the electromagnetic characteristics of ultra-high voltage (UHV) transformers under DC Bias, a specifically designed scaling transformer is considered for the measurement of the actual distorted exciting current. Meanwhile, the equivalent numerical model based on the Finite element method (FEM) and the field-circuit coupled modelling is adopted. The comparison between the measurement and the simulation results of exciting current shows that the difference is negligible. Based on these fundamental data, exponential function is used to fit the relationship between the distorted exciting current peak and DC current. Therefore, through this relationship, the corresponding condition of exciting current can be assessed in ever-changing circumstances. This assessment method has great advantages in terms of computational speed and accuracy, which enables to give a promising prospect in engineering calculation.

Original languageEnglish
Title of host publication2018 Condition Monitoring and Diagnosis, CMD 2018 - Proceedings
EditorsAhmed Abu-Siada
PublisherInstitute of Electrical and Electronics Engineers Inc.
ISBN (Electronic)9781538641262
DOIs
StatePublished - 14 Nov 2018
Externally publishedYes
Event7th International Conference on Condition Monitoring and Diagnosis, CMD 2018 - Perth, Australia
Duration: 23 Sep 201826 Sep 2018

Publication series

Name2018 Condition Monitoring and Diagnosis, CMD 2018 - Proceedings

Conference

Conference7th International Conference on Condition Monitoring and Diagnosis, CMD 2018
Country/TerritoryAustralia
CityPerth
Period23/09/1826/09/18

Keywords

  • Condition Assessment
  • DC Bias
  • Exciting Current
  • Field-circuit coupled
  • UHV Transformer

Fingerprint