Skip to main navigation Skip to search Skip to main content

An experimental study on the air side heat transfer performance of the perforated fin-tube heat exchangers under the frosting conditions

  • Xi'an Jiaotong University

Research output: Contribution to journalArticlepeer-review

50 Scopus citations

Abstract

In this paper, perforated fins were applied to enhance the air side heat transfer performance under frosting conditions for fin-tube heat exchangers with large fin pitches. The frost mass, frost thickness, heat transfer rate and heat transfer coefficient of the perforated fin-tube heat exchangers were measured and analyzed. Although, the frost mass for the perforated fin-tube heat exchangers was 46.7% more than that for the plain fin. The total heat transfer rate and the heat transfer coefficient of the perforated fin was increased by 38.9% and 31.8%. Moreover, under the same heat transfer rate, the heat exchangers with the perforated fins generated less frost mass compared with the plain fin. Two empirical correlations for predicting the j-factor and frost mass of the perforated fin-tube heat exchangers were developed respectively. The correlations were functions of the Reynold number, dimensionless fin pitch, dimensionless temperature, and humidity and Fourier number. The deviations between these predictions and the corresponding measured experimental data fell within ±15.0%.

Original languageEnglish
Article number114634
JournalApplied Thermal Engineering
Volume166
DOIs
StatePublished - 5 Feb 2020

Keywords

  • Empirical correlation
  • Finned-tube heat exchanger
  • Frosting
  • Perforation

Fingerprint

Dive into the research topics of 'An experimental study on the air side heat transfer performance of the perforated fin-tube heat exchangers under the frosting conditions'. Together they form a unique fingerprint.

Cite this