Algorithm to calculate the excitation inductance of power transformer with Y-Delta connection

  • Jiale Suonan
  • , Zaibin Jiao
  • , Guobing Song
  • , Yining Zhang
  • , Xiaoning Kang

Research output: Contribution to journalArticlepeer-review

13 Scopus citations

Abstract

A computational method of excitation inductance of power transformer needs current of all windings. However the excitation inductance of power transformer with Y-Delta connection cannot be calculated directly using any existed method because the winding currents on the Delta side cannot be measured based on existed TA. An algorithm to calculate the excitation inductance of power transformer with Y-Delta connection is proposed. Based on the equivalent circuit equation, the excitation inductance of power transformer with Y-Delta connection is calculated by using the line currents on the Delta side directly and by eliminating the internal currents of windings on the Delta side. The algorithm accuracy is verified by electromagnetic transients program (EMTP) simulation. The result shows that the excitation inductance calculated using the proposed algorithm can reflect the transformer and its iron core status accurately, effectively and sensitively. It can be used as the criterion of transformer protection and has good project application prospect in the field of the transformer protection.

Original languageEnglish
Pages (from-to)32-36+67
JournalDianli Xitong Zidonghua/Automation of Electric Power Systems
Volume31
Issue number9
StatePublished - 10 May 2007

Keywords

  • Circulation current at delta side
  • Differential protection
  • Excitation inductance
  • Magnetic inrush current
  • Power transformer with Y-Delta connection

Fingerprint

Dive into the research topics of 'Algorithm to calculate the excitation inductance of power transformer with Y-Delta connection'. Together they form a unique fingerprint.

Cite this