Aging assessment of large generator insulation based on PD measurements

Research output: Contribution to journalArticlepeer-review

5 Scopus citations

Abstract

The statistical parameters of phase resolved partial discharge (PD) distribution and ultra-wideband (UWB) characteristics of PD pulse are proposed for aging assessment of large generator insulation. Multi-stress aging tests of the model generator stator bar specimens were performed and PD measurements were conducted using both digital PD detector with frequency ranging from 40 kHz to 400 kHz and UWB PD detector with bandwidth from 10 MHz to 3 GHz at different aging stages. The test results show that the skewness and UWB frequency characteristics of PD can be taken as the characterization parameters for aging assessment of generator insulation. Furthermore, the measurement results of real generator stator bars show that these methods based on statistical parameters and UWB characteristics of PD are prospective for aging assessment and residual lifetime estimation of large generator stator insulation.

Original languageEnglish
Pages (from-to)1035-1043
Number of pages9
JournalProgress in Natural Science
Volume15
Issue number11
DOIs
StatePublished - Nov 2005

Keywords

  • Aging assessment
  • Multi-stress accelerated aging
  • Partial discharge
  • Statistical parameters
  • Stator insulation
  • Ultra-wideband

Fingerprint

Dive into the research topics of 'Aging assessment of large generator insulation based on PD measurements'. Together they form a unique fingerprint.

Cite this