Abstract
Aiming at low reliability in short-time energy analysis method for on-line monitoring of circuit breaker mechanical state, the paper studies the method to eliminate interference noise by using trip coil current signal to improve the reliability of short-time energy analysis method. According to the analysis of vibration signal, this method can significantly improve the reliability of short-time energy analysis method to get the commencement instant of the vibration event from an adverse environment by rejecting most of the noise. The method is also compared with wavelet packets extraction algorithm. The method is tested on a ZN12-35 type vacuum circuit breaker and accurate switching synchronization status of the circuit breaker is obtained. The test results show that the new method obviously improve the accuracy of short-time energy analysis method to get the switching synchronization status of circuit breaker.
| Original language | English |
|---|---|
| Pages (from-to) | 139-144 |
| Number of pages | 6 |
| Journal | Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering |
| Volume | 28 |
| Issue number | 12 |
| State | Published - 25 Apr 2008 |
Keywords
- Circuit breaker
- Short-time energy
- Trip coil
- Vibration signal
Fingerprint
Dive into the research topics of 'A novel on-line monitoring method for three phase synchronization of medium voltage vacuum circuit breaker'. Together they form a unique fingerprint.Cite this