T1 - A new method of on-line medium frequency partial discharge monitoring for power transformer based on double sensors directionally coupling signal
AU - Liao, Yancqun
AU - Xu, Yang
AU - Qiu, Changrong
AU - Xi, Baofeng
AU - Liu, Xinying
AU - Feng, Yi
AU - Fang, Qiong
PY - 2007
Y1 - 2007
N2 - This paper introduces an on-line monitoring method for power transformers, using double magnetic core current sensors directionally coupling signal to limit interference using a polarity discrimination method. The transient models of transformer windings are set up, and considering the characteristic of the current sensors and transformer windings, the testing frequency band is chosen from 1MHz to3MHz. The reliability of polarity discrimination method to limit interference is verified over this frequency range.
AB - This paper introduces an on-line monitoring method for power transformers, using double magnetic core current sensors directionally coupling signal to limit interference using a polarity discrimination method. The transient models of transformer windings are set up, and considering the characteristic of the current sensors and transformer windings, the testing frequency band is chosen from 1MHz to3MHz. The reliability of polarity discrimination method to limit interference is verified over this frequency range.
UR - https://www.scopus.com/pages/publications/47349093113
U2 - 10.1109/ICSD.2007.4290884
DO - 10.1109/ICSD.2007.4290884
M3 - 会议稿件
AN - SCOPUS:47349093113
SN - 1424407516
SN - 9781424407514
T3 - 2007 International Conference on Solid Dielectrics, ICSD
SP - 596
EP - 599
BT - 2007 International Conference on Solid Dielectrics, ICSD
T2 - 2007 International Conference on Solid Dielectrics, ICSD
Y2 - 8 July 2007 through 13 July 2007
ER -