Skip to main navigation Skip to search Skip to main content

高压XLPE绝缘电力电缆护层烧蚀机理分析

Translated title of the contribution: Ablation Mechanism Analysis on Metal Sheath of High Voltage XLPE Insulated Power Cable
  • Songlin Zhou
  • , Ruoxi Liu
  • , Lei Jiang
  • , Hongliang Liu
  • , Huachun Li
  • , Zhigang Ren
  • , Yue Xin
  • , Lisheng Zhong
  • , Jinghui Gao
  • State Grid Beijing Electric Power Research Institute
  • Xi'an Jiaotong University

Research output: Contribution to journal › Article › peer-review

21 Scopus citations

Abstract

In this paper, a case of 110 kV cable fault is analyzed. After investigating ablation morphology, cable structure and its operating environment, the causes of ablation, such as the bad connect between buffer layer and corrugated aluminum (Al) sheath as well as the inductive voltage on metal sheath, are put forward. To verify the reasonableness of the above two causes, a simulation model of 110 kV cable is established, a model sample of corrugated Al sheath is designed and an ablation simulation experiment is carried out. For further exploring the Al sheath discharge condition and law, the initial discharge voltage of the model sample under different gaps is tested, which further demonstrates the above ablation mechanism. The research results of this paper can provide an effective guide for cable design and fault analysis.

Translated title of the contributionAblation Mechanism Analysis on Metal Sheath of High Voltage XLPE Insulated Power Cable
Original languageChinese (Traditional)
Pages (from-to)171-176
Number of pages6
JournalGaoya Dianqi/High Voltage Apparatus
Volume56
Issue number12
DOIs
StatePublished - 16 Dec 2020

Fingerprint

Dive into the research topics of 'Ablation Mechanism Analysis on Metal Sheath of High Voltage XLPE Insulated Power Cable'. Together they form a unique fingerprint.

Cite this