Skip to main navigation Skip to search Skip to main content

翻转角度对雷达阵面翻转式插箱空调热管理影响的实验研究

Translated title of the contribution: Experimental Study of the Effect of Tilt Angle on the Thermal Management of Radar Array Flip-Flop Plug-in Box Air Conditioners
  • National Innovation Platform (Center) for Industry-Education Integration of Energy Storage Technology
  • Ltd.
  • Xi'an Jiaotong University

Research output: Contribution to journalArticlepeer-review

Abstract

To cnsure that the thermal management System functions effectively during changcs in gravitational flipping angle during the work process of the radar antenna array, a rotatable plug-in box-typc air conditioning experimental rig is developcd. Through the Simulation of the working process of the radar antenna array, the dynamic operating characteristics of the rotatable plug-in box-type air conditioners arc analyzed. Variations in System Performance under different tilt angles are determined, and the dynamic distribution of refrigerant and its impact on electronic device thermal management is investigated. The rcsults demonstrated that the air conditioning System remains highly rcliablc under tilted conditions. Compared to the non-tilted State, the System showed minor Performance decreases but maintained stable Operation under the flipping working condition. The maximum reduetions in cooling capacity for forward and backward tilts of 90° wcrc 0. 29% and 6. 48% > respectively, while the maximum reductions in the coefficient of Performance wcrc 4. 11% and 6. 02%, respectively. Furthermorc, the refrigerant distribution is highly affected by gravity; forward and backward tilts of 90° rcsultcd in uncvcn refrigerant distribution within the evaporator, whereas left and right tilts of 90° had ncgligiblc effects. These findings offer theoretical and practical reference for the design and application of plug-in box-type air conditioning Systems for radar arrays.

Translated title of the contributionExperimental Study of the Effect of Tilt Angle on the Thermal Management of Radar Array Flip-Flop Plug-in Box Air Conditioners
Original languageChinese (Traditional)
Pages (from-to)97-106
Number of pages10
JournalHsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University
Volume59
Issue number5
DOIs
StatePublished - May 2025

Fingerprint

Dive into the research topics of 'Experimental Study of the Effect of Tilt Angle on the Thermal Management of Radar Array Flip-Flop Plug-in Box Air Conditioners'. Together they form a unique fingerprint.