特高压直流套管气-固界面长时闪络放电特性及其影响因素

Translated title of the contribution: Long-time Flashover Discharge Characteristics of Gas-solid Interface of UHVDC Bushing and its Influencing Factors
  • Shuqi Zhang
  • , Jinzhong Li
  • , Hao Tang
  • , Xining Li
  • , Yi Zhang
  • , Bo Qi
  • , Jiaxuan Yan

Research output: Contribution to journalArticlepeer-review

6 Scopus citations

Abstract

The gas-solid interface between SF6 gas and the epoxy resin-impregnated paper capacitor core inside the resin-impregnated paper bushing (RIP Bushing) is the weak point of insulation inside the bushing where discharges are likely to occur. In order to study the long-time flashover discharge characteristics and its influencing factors at the gas-solid insulation interface inside the dry-type bushing, we build an experimental platform for flashover characteristics, and test the surface charge distribution of epoxy-impregnated paper specimens under the influence of different surface states and particles, revealing the influence mechanism of various factors on the surface electric field and flashover characteristics. At the same time, a long-time pressurization experiment is conducted to obtain the discharge characteristics by manufacturing defects core specimens. The results show that there are highly dispersed fiber protrusions at the gas-solid interface of the bushing in the high-voltage side area, in which particles can be easily attracted during operation. Under the action of DC voltage, charge accumulation and electric field distortion will cause weak initial partial discharge. Besides, the long-term voltage action intensifies the charge accumulation, further increases the degree of electric field distortion, gradually increases the frequency and amplitude of PD, and eventually leads to penetrating flashover discharge. The research results can provide theoretical and experimental basis for optimization of the surface treatment process of the resin-impregnated paper bushing capacitor core and the formulation of the suppression measures for flashover discharge under long-term direct current.

Translated title of the contributionLong-time Flashover Discharge Characteristics of Gas-solid Interface of UHVDC Bushing and its Influencing Factors
Original languageChinese (Traditional)
Pages (from-to)5776-5786
Number of pages11
JournalZhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
Volume44
Issue number14
DOIs
StatePublished - 20 Jul 2024
Externally publishedYes

Fingerprint

Dive into the research topics of 'Long-time Flashover Discharge Characteristics of Gas-solid Interface of UHVDC Bushing and its Influencing Factors'. Together they form a unique fingerprint.

Cite this