Abstract
Virtual synchronous generator control can realize the active power sharing between parallel inverters in steady state. However, the difference of inertia, damping or line impedance may cause active power overshoot and oscillation. In this paper, the active power transient process during load transition is divided into two stages. The characteristics of the two stages are analyzed by the equivalent circuit model and the small signal model model respectively. On this basis, the transient active power sharing optimization method based on virtual impedance and transient damping is proposed. Finally, the Matlab/Simulink simulation and experimental results validate the availability of the proposed method.
| Translated title of the contribution | Analysis and Optimal Control of Transient Active Power Sharing between Islanded Parallel Virtual Synchronous Generators |
|---|---|
| Original language | Chinese (Traditional) |
| Pages (from-to) | 654-663 |
| Number of pages | 10 |
| Journal | Diangong Jishu Xuebao/Transactions of China Electrotechnical Society |
| Volume | 34 |
| DOIs | |
| State | Published - 25 Nov 2019 |
Fingerprint