太阳能辅助地源热泵联合供暖系统模拟研究

Translated title of the contribution: Numerical study on the combined heating system of a ground-source heat pump assisted by the solar energy

Research output: Contribution to journalArticlepeer-review

5 Scopus citations

Abstract

In order to solve the high energy consumption of buildings in cold season, a ground-source heat pump assisted by the solar photovoltaic/thermal system (PV/T-GSHP) can be used. A civil building in Beijing was taken as the research object. The transient system simulation code TRNSYS was adopted to analyze the PV/T-GSHP system performance during heating season (November 2018 to March 2019). Four different temperature control strategies were established based on the local climatic conditions and performance parameters of system equipments. The numerical results were also compared with those of the traditional ground-source heat pump (GSHP) system. The results indicate that the photoelectric and photothermal conversion efficiencies of the PV/T system reach 15.0% and 46.6%, respectively. Compared with the tradional GSHP system, the coefficient of performance and the overall coefficient of performance of the system are increased by 6.9% and 10.3%, respectively. The soil temperature drop of the PV/T-GSHP system is only 8.0% according to a long-term simulation of 10 years.

Translated title of the contributionNumerical study on the combined heating system of a ground-source heat pump assisted by the solar energy
Original languageChinese (Traditional)
Pages (from-to)111-117
Number of pages7
JournalShanghai Ligong Daxue Xuebao/Journal of University of Shanghai for Science and Technology
Volume43
Issue number2
DOIs
StatePublished - Apr 2021

Fingerprint

Dive into the research topics of 'Numerical study on the combined heating system of a ground-source heat pump assisted by the solar energy'. Together they form a unique fingerprint.

Cite this