Skip to main navigation Skip to search Skip to main content

基于GIC无功损耗严重度指标的电网地磁暴易损区识别方法

Translated title of the contribution: Identification method of power system geomagnetic storm vulnerable area based on GIC reactive power loss
  • Yini Xu
  • , Xiaoning Kang
  • , Chong Zhao
  • , Mingda Guo
  • , Gengfeng Li
  • Xi'an Jiaotong University

Research output: Contribution to journalArticlepeer-review

3 Scopus citations

Abstract

The change rules of reactive power loss of substations under different geo-electric intensity and direction are analyzed and then the GIC(Geomagnetically Induced Current) reactive power loss severity index of substation is defined. The index only normalizes the actual reactive power losses and does not change the relative relationship of reactive power loss among substations. Based on the index, an identification method for the areas susceptible to geomagnetic storms in a given system is proposed, which can provide a basis for grid planning and operation under the influence of geo-magnetic storms. Finally, a planned 750kV power system is taken as an example to verify the feasibility of the proposed index and algorithm.

Translated title of the contributionIdentification method of power system geomagnetic storm vulnerable area based on GIC reactive power loss
Original languageChinese (Traditional)
Pages (from-to)211-216
Number of pages6
JournalDianli Zidonghua Shebei/Electric Power Automation Equipment
Volume39
Issue number11
DOIs
StatePublished - 10 Nov 2019

Fingerprint

Dive into the research topics of 'Identification method of power system geomagnetic storm vulnerable area based on GIC reactive power loss'. Together they form a unique fingerprint.