Abstract
During long-term use of a circuit breaker, the over-travel will change due to contact wear, screw loosening, etc. which makes the determination of circuit breaker’s opening/closing instant difficult. To obtain an accurate judgment method of the opening and closing instants in the case of over-travel variation, this research took a 12 kV AC medium-voltage vacuum circuit breaker as the object of study to build an off-line test platform for monitoring the circuit breaker’s mechanical condition. Firstly, after simulation of different over-travels, the transposition signal of contactor and the vibration signal in opening/closing process of the circuit breaker were collected synchronously. Then, the short-time energy method was used to process the vibration signal and analyze the corresponding relationship between the opening and closing instants extracted from the transposition signal and the characteristic quantities extracted from the vibration signal. The vibration signal is used to replace the transposition signal so as to exactly determine the opening and closing instants and accurately calculate the opening and closing time through extraction of the vibration signal in the opening and closing process of the circuit breaker. The result shows that under variation of the over-travel, this method can reduce the judgment error of the opening and closing instants to 0.5 ms, which means that it improves the accuracy of the monitoring results. This research may provide a reliable and accurate method for on-line monitoring of mechanical condition of circuit breakers.
| Translated title of the contribution | Identification Method of Opening/Closing Instant of Circuit Breaker Under Over-travel Variation Based on Vibration Signal |
|---|---|
| Original language | Chinese (Traditional) |
| Pages (from-to) | 184-190 |
| Number of pages | 7 |
| Journal | Gaoya Dianqi/High Voltage Apparatus |
| Volume | 55 |
| Issue number | 11 |
| DOIs | |
| State | Published - 16 Nov 2019 |
Fingerprint
Dive into the research topics of 'Identification Method of Opening/Closing Instant of Circuit Breaker Under Over-travel Variation Based on Vibration Signal'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver