减小电压暂降深度及持续时间的单相重合闸时序方案

Translated title of the contribution: Single-phase Reclosing Sequence for Reducing Voltage Sag Depth and Duration
  • Zhenfeng Liang
  • , Qing Zhang
  • , Guobing Song
  • , Zhanfeng Fan
  • , Baowei Li

Research output: Contribution to journalArticlepeer-review

6 Scopus citations

Abstract

In order to reduce the voltage sag depth and duration of sensitive load when the single-phase circuit breaker reclosing fails, a scheme of single-phase reclosing sequence is proposed. When a single-phase grounding fault occurs on the line, the protections on both sides act and fault phase breakers are tripped. The concept of fault component is used to construct the fault additional state network. Additional source is added to each end of the line to calculate the fault component voltage of the sensitive load node. The reclosing sequence is determined according to the magnitude of fault component voltage of sensitive load node. The side with smaller magnitude is determined to reclose first. After one side of the line is reclosed, the magnitude of line voltage is used to judge whether the reclosing is open or not at the other side. PSCAD/EMTDC simulation results show that this method is not affected by transition resistance and fault location and can improve the voltage power quality of sensitive load.

Translated title of the contributionSingle-phase Reclosing Sequence for Reducing Voltage Sag Depth and Duration
Original languageChinese (Traditional)
Pages (from-to)165-170
Number of pages6
JournalDianli Xitong Zidonghua/Automation of Electric Power Systems
Volume43
Issue number9
DOIs
StatePublished - 10 May 2019

Fingerprint

Dive into the research topics of 'Single-phase Reclosing Sequence for Reducing Voltage Sag Depth and Duration'. Together they form a unique fingerprint.

Cite this