Skip to main navigation Skip to search Skip to main content

一种应对高阻故障的单端自适应行波保护方法

Translated title of the contribution: A Non-unit Adaptive Traveling Wave Protection Method for High Impedance Faults
  • Xi'an Jiaotong University
  • Tsinghua University

Research output: Contribution to journalArticlepeer-review

47 Scopus citations

Abstract

The traditional derivative-based traveling wave protection method has the problem of operation failure when the high impedance faults occur. Based on the analysis of the influence factors of the fault traveling wave, this paper draws the conclusion that the distortion of fault traveling wave is related to the fault distance, and the amplitude of fault traveling wave is related to fault impedance. A basic fitting function was proposed to fit the zero-mode fault current, and the parameters reflecting fault distance and impedance were obtained. The fault impedance estimation interval can be obtained by extracting fault information from the obtained parameters, and the adaptive non-unit traveling wave protection method was realized. The simulation results show that the proposed method can protect the DC transmission line fast and effectively, even with high fault impedance. Comparing with the traditional traveling wave protection and transient-based protection, the proposed method has higher sensitivity and can protect wider area of the DC transmission lines.

Translated title of the contributionA Non-unit Adaptive Traveling Wave Protection Method for High Impedance Faults
Original languageChinese (Traditional)
Pages (from-to)3548-3556
Number of pages9
JournalZhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
Volume40
Issue number11
DOIs
StatePublished - 5 Jun 2020

Fingerprint

Dive into the research topics of 'A Non-unit Adaptive Traveling Wave Protection Method for High Impedance Faults'. Together they form a unique fingerprint.

Cite this